15 - 38 kV HV Capacitor Bank - Power factor switching

VersaVac switch

The VersaVac (VSV) is a long life vacuum switch used for pole top Capacitor switching.

The VSV was specifically designed to replace oil switches to eliminate costly maintenance.

The VSV can be used as a direct replacement on existing banks or supplied by manufacturers on new banks. Joslyn's unique design incorporates Joslyteš , the field proven solid dielectric foam that has been successfully used over 35 years.

Peak Power - Joslyn

Specifications

Voltage Class (kV) 15 27 38
Maximum Voltage      
- Solid Grounded Applications (kV) 15.5 27.5 38
-  ngrounded Applications (kV) 15.5 27.5 N/A
-  ngrounded Applications with Manual Trip (kV) 12.47 22.5 N/A
Impulse Withstand (kV BIL)      
- Line to Ground 95 125 150
- Open-Gap 95 95/125 125
Power Frequency AC Withstand Dry/Wet (kV RMS) 36/60 60/50 70/60
Units equipped with manual trip handle.      
Application Grounded or Ungrounded  
General Style VerSaVac Single-Phase Distribution Switch
  Material Porcelain / Epoxy
Dimension Information Interrupter Module Assembly Height Inches (MM) 18 (457.2)
  Terminal to Terminal Height Inches (MM) 8 15/16 (227.0)
  Total Height Inches (MM) 27 5/8 (701.7)
Specifications Weight LBS. (KG) 30.8 (14.0)
  Number of Pins in Connector 5
Ratings Exceeds Electrical Requirements of ANSI C37.66  
  Continuous Current 200A
  Short-Time Current 6kA (1/2 sec.), 4.5kA (1 sec.)
  Asymmetrical Momentary/Making Current 9kA Asymmetrical RMS/23kA Peak
  Peak Inrush Current Limit for Parallel or Back-to-Back Switching Applications 6kA
  Control Voltages 120VAC, 240VAC
  Minimum Operating Voltage 80VAC, 160VAC
  Recommended Control Pulse Time 100 msec.
  Auxiliary Contact Rating 15A 120VAC, 0.5A 125VDC
Accessories Junction Boxes, Cable Assemblies, Current Sensors, Mating Connectors, Animal Protectors (2 per switch), Undervoltage Trip Control, Zero Voltage Closing (ZVC) Control, 125 DC Control Interface